Control switches accurately monitor liquid levels to activate pump control panels and alarms.
The Sensor Float® control switch is used to accurately monitor high (normally open) or low (normally closed) liquid levels to activate pump control panels and alarms in non-potable water and sewage applications.
Normally Open Models (high level): The control switch turns on (closes) when the float tips slightly above horizontal signaling a high level and turns off (opens) when the float drops slightly below horizontal.
Normally Closed Models (low levels): The control switch turns on (closes) when the float tips slightly below horizontal signaling a low level and turns off (opens) when the float tips slightly above horizontal.
This switch is not sensitive to rotation and is suitable for use with intrinsically safe circuits. Contact SJE-Rhombus regarding specific intrinsically safe applications.
Features:
Options:
UL Listed, CSA Certified
Three Year Limited Warranty
Specifications:
CABLE:
Flexible 18 gauge, 2 conductor (UL, CSA) SJOW, water-resistant (CPE) jacket
FLOAT:
3.38 inches diameter x 4.55 inches long (8.58 x 11.56 cm) high impact, corrosion resistance, PVC housing for use in sewage and non-potable water up to 140oF (60oC)
MAXIMUM WATER DEPTH:
30 feet (9 meters), 13 PSI (90 kPa)
MERCURY TILT SWITCH:
Single pole, single throw, mercury-to-mercury contacts, hermetically sealed in a steel capsule and epoxy sealed in the float housing
ELECTRICAL:
5 amps, 120/230 VAC, 50/60 Hz
Adobe Acrobat is a free download to view .pdfs
Visit our downloads section of this website for additional literature.